FILED: BROOME COUNTY CLERK 07/15/2022 01:46 PM INDEX NO. EFCA2011001832
NYSCEF DOC. NO. 263 RECEIVED NYSCEF: 07/15/2022
EXHIBIT “E”
FILED: BROOME COUNTY CLERK 07/15/2022 01:46 PM INDEX NO. EFCA2011001832
NYSCEF DOC. NO. 263 RECEIVED NYSCEF: 07/15/2022
I
I
SECTION 16051
I
WIRING FOR CONTROLLERS
I (FOR INSTURMENTA TION (I) ORAWINGS)
I PART 1 GENERAL
1.01 SUMMARY
I
A. Section includes building wire and cable; EMT conduit, rigid steel conduit; and
wiring connectors and connections.
I
1.02 REFERENCES
I A. International Electrical Testing Association:
1. NETA ATS - Acceptance Testing Specifications for Electrical Power
Distribution Equipment and Systems.
I 1.03 DESIGN REQUIREMENTS
A. Conductor sizes are based on copper.
I
B. No aluminum conductor to be substituted.
I 1.04 SUBMIITALS
A. Section 0 1 3 3 0 - Submittal Procedures: Requirements for submittals.
I
B. Product Data: Submit for building wire and each cable assembly type.
I C. Samples:
1. Submit I each, 1 8 inch length of cable assembly from each reel.
2. Select each length to include complete set of manufacturer markings.
I 3. Attach tag indicating cable size and application information.
D. Test Reports: Indicate procedures and values obtained.
I
1.05 CLOSEOUT SUBMITI ALS
I A. Section 01700 - Execution Requirements: Requirements for submittals.
B. Project Record Documents: Record actual locations of components and circuits.
I
I
I 2000.099.001 16051-1 189.019.002
FILED: BROOME COUNTY CLERK 07/15/2022 01:46 PM INDEX NO. EFCA2011001832
NYSCEF DOC. NO. 263 RECEIVED NYSCEF: 07/15/2022
I
I
1.06 QUALIFICATIONS
I
A. Manufacturer: Company specializing in manufacturing products specified in this
section with minimum three years documented experience.
I
1.07 FIELD MEASUREMENTS
A. Verify field measurements.
I
1.08 COORDINATION
A. Section 0 1 3 0 0 - Administrative Requirements: Requirements for coordination.
I
B. Wire and cable routing indicated is approximate unless dimensioned.
I
PART 2 PRODUCTS
I
2.01 FOUNDATION FIELD BUS CABLE:
A. Cable shall meet ISA/SP50 requirements for type A cable. I
B. Cables shall be rated for -40 degrees C to I 05 degrees C and be sunlight resistant.
I
C. Twisted, shielded pair, wire size 18awg, 100 ohm characteristic impedance and a
resistance of 7.35 ohms per 100ft.
I
D. Refer to drawing 1005-A for distances and additional information on Foundation
Field Bus Cable.
I
2.02 DEVICE NET TRUNK LINE (HIGH FLEX):
A. Physical Characteristics:
I
1. Two shielded pairs-common axis with drain wire in center and
polypropylene fillers.
2. Overall braid shield -- 65% coverage 36 AWG CU braid, 45 degree angle
I
wrap individually tinned.
B. Drain Wire - # 1 8 (65 X 36 AWG) copper (individually tinned).
I
C. Outer Diameter- 0.475 =/- 0 . 0 1 5 inches.
D. Jacket Insulation - .068 inches nominal, light gray PVC.
I
E. Jacket Marking- (Devicenet Trademark, Drawing #75010-004) high flex thick
cable 1485CF-Pl-A 1PR16 1PR18 sheilded (UL) E34972 CMG 75C or PLTC
I
300V or AWM 2464 BOC C(UL) CMG or AWM 1/11 A 80C 300V ft4.
I
2000.099.001 16051-2 189.019.002
I
FILED: BROOME COUNTY CLERK 07/15/2022 01:46 PM INDEX NO. EFCA2011001832
NYSCEF DOC. NO. 263 RECEIVED NYSCEF: 07/15/2022
I
I
F. Electrical Character:
1. OCR (braid+tape+drain) - 1 . 8 8 Ohms/1000ft. (nom. @ 20 degrees C. ).
Applicable Environmental Characteristics:
'
G.
I 1. Flame resistance - UL 1 5 8 1 Vertical Tray CSA FTl
2. Oil resistance - UL 1277, Oil Resistance II
3. Agency Certifications - NEC (UL) PLTC 300V 75C or CM 75C AWN
I 2464 SOC, C(UL)CM 75C, CSA Awm /11 A SOC 300V.
4. Flexure - S-Bend Flex Test: Approx. 360,000 cycles +/- 90 degree flex
test: Approx 700,000 cycles
I 5. Bend Radius Installation/fixed - 20 x diameter/ 1 0 x diameter.
6. Operating ambient temperature - -20 to +60C @ 8 amps for 1 6 awg, 5
,
,
amps for 1 8 awg: derate current linearly to zero at 80C.
7. Storage temperature - -40 to +85C.
8. Pulling tension - 205 lbs max.
i H. Refer to drawing 1004-A for additional information.
2.03 DEVICE NET DROP LINE (HIGH FLEX)
f
A. Physical Characteristics:
1. Two shielded pairs -- common axis with drain wire in center and
I polypropylene fillers.
2. Overall braid shield - 65% coverage 36 AWO CU braid, 45 degree angle
wrap with non-hydroscopic wrap (individually tinned)
I 3. Drain Wire - #22 ( 1 9 x 36 AWO) copper (individually tinned).
4. Outer Diameter- 0.270 +/- 0 . 0 1 0 inches.
5. Jacket Insulation- .030 inches nominal yellow- CPE.
I 6. Jacket Marking- (UL) CL2 or CM 75C or AWM 20869 80C (Devicenet
Trademark, Drawing #75010-004) thin cable 1485C-P1-C (UL file
number) lpr22, lpr24 shielded or C(UL) cm75C.
I
B. Electrical Character:
1. DCR(braid+tape+drain) - 3.2 Ohms/1000ft (nom. @ 20 degrees C.)
t
C. Applicable Environmental Characteristics
I 1. Flame Resistance - UL 1581 Vertical Tray CSA FTl
2. Oil Resistance- UL 1277. Oil Res II
3. Agency Certifications -- NEC (UL) CL2 or CM 75C, A WM 20869 80C, C
I (UL) CM75C, CSA AWM 1/ 1 1 A/B 80C 300V.
4. Flexure - TBD cycles at xl 0 bend radius.
5. Bend Radius installation/fixed - 20 x diameter/ 7 x diameter.
I 6. Operating ambient temperature - -20 to +70 C @ 1.5amps derate current
linearly to zero to SOC.
l
I 2000.099.001 16051-3 189.019.002
eo e n A A t A
FILED: BROOME COUNTY CLERK 07/15/2022 01:46 PM INDEX NO. EFCA2011001832
NYSCEF DOC. NO. 263 RECEIVED NYSCEF: 07/15/2022
I
I
7. Storage temperature - -40 to +85C.
8. Pulling tension -- 65 lbs. Max. I
D. Refer to drawing 1004-A for additional information.
I
2.04 CONTROLNET
A. Communication :
I
1. ControlNet -- Redundant media and network access port -- Foundation
Fieldbus H l (2 independent channels- LAS on both channels, Time
I
Master on both channels).
B. Power Requirements:
1. 1 1 - 3 0 V dc; 270 m A @ 24V dc (typical).
I
'
C. Indicators:
1. Module Status -- Fieldbus Status, 1 per channel -- ControlNet Status, I per
i
connection
D. Connectors:
I.,,
I. ControlNet - BNC connectors -- Network Access Port -- RJ45 - Fieldbus -
9 pin sub-D connectors.
I
E. Conductors/Wire Size/Category:
1. Category 2
I
F. Mounting:
·I
1. 35mm DIN rail.
G. ControlNet Channel Selection:
1. Two 1 0 position rotary switches.
I
H. Vibration (Operating):
1. 2G per axis. I
I. Environmental:
1. Operating Temperature: 0 to 60 degree C. (32 to 140 degrees F.) I
2. Storage Temperature: -40 to 85 degrees C. (-40 to 1 8 5 degrees F.)
3. Relative Humidity: 5 to 90% (without condensation)
l
J. Agency Certification (when product is marked):
1. Information technology Equipment
2. Industrial Control Equipment I
3. Class I, Div. 2, Groups A, B, C, D.
1·
2000.099.001 160514 189.019.002
I
FILED: BROOME COUNTY CLERK 07/15/2022 01:46 PM INDEX NO. EFCA2011001832
NYSCEF DOC. NO. 263 RECEIVED NYSCEF: 07/15/2022
I
I
4. Hazardous Location
I a. EN 50082-1, 2
b. EN 55022, Radiated Emission Class B
c. EN 6 1 1 3 1 - 2
t d. FCC Part 1 5 , SubPart B
I PART 3 EXECUTION
3.01 EXAMINATION
I
A. Section 0 1 3 0 0 - Administrative Requirements: Coordination and project
conditions.
I B. Verify interior of building has been protected from weather.
i C. Verify mechanical work likely to damage wire and cable has been completed.
D. Verify raceway installation is complete and supported .
I 3.02 PREPARATION
A. Completely and thoroughly swab raceway before installing wire.
,I
3.03 INSTALLATION
I A. Route wire and cable to meet Project conditions.
B. Neatly train and lace wiring inside boxes, equipment, and panelboards.
I
C. Identify and color code wire and cable under provisions of Section 1607 5.
Identify each conductor with its circuit number or other designation indicated.
l
D. Special Techniques--Building Wire in Raceway:
,, 1. Pull conductors into raceway at same time.
E. Special Techniques - Cable:
1. Protect exposed cable from damage.
I 2. Support cables above accessible ceiling, using spring metal clips or metal
cable ties to support cables from structure or ceiling suspension system.
Do not rest cable on ceiling panels.
I 3. Use suitable cable fittings and connectors.
F. Special Techniques - Wiring Connections:
l 1. Clean conductor surfaces before installing lugs and connectors.
I
I 2000.099.001 16051-5 189.019.002
FILED: BROOME COUNTY CLERK 07/15/2022 01:46 PM INDEX NO. EFCA2011001832
NYSCEF DOC. NO. 263 RECEIVED NYSCEF: 07/15/2022
f
t
2. Make splices, taps, and tenninations to carry full ampacity of conductors
with no perceptible temperature rise. I
3.04 FIELD QUALITY CONTROL
I
A. Section 01700 - Execution Requirements: Testing, adjusting, and balancing.
B. Inspect and test in accordance with NET A ATS, except Section 4.
I
\
END OF SECTION